VE.Net Generator monitoring
The generator control module adds a huge number of
features to your on board generator. It monitors AC
voltage, current, kilowatts and frequency, DC voltage,
oil pressure, water temperature and engine speed. All of
this data is transmitted over the network. This allows the
generator to be controlled and monitored from a remote
location in the event that a GSM web module forms part
of the system.
Generator warranty retained
The standard controls on the generator are retained to
ensure that your generator warranty is unaffected.
Auto start capability
The VE.Net module adds “auto start” capability.
This means that the generator start up routine of pre-heat
and cranking (until the engine res) are automated.
The module can start the generator from a VE.Net signal
or hard-wired momentary or latching contacts.
Alarms
Most of the monitored parameters can be allocated to
alarms. These alarms can be congured as VE.Net alarms
to alert to user or to alarm and shutdown automatically.
Load shedding
An optional upgraded sensor module incorporates a load
shedding contactor. This enables the use of a warm up
and cool down period. The sensor module caters for
generators up to 50 amps. Above this size an installer will
have to use an external contactor.
Supported generator brands
As generator control systems vary there is a list of
generator types to select from. This will be extended as
more brands are catered for.
VE.Net Generator Module
Power supply voltage
range
7 - 32 V DC
Maximum current
consumption
30 mA / 12 V - 15 mA / 24 V
INPUTS
Battery Voltage 7,0 - 32,0 V
AC Amperage
(via external CT)
0 - 100 A
AC Voltage (via external
drop down transformer)
0 - 300 V
Engine Coolant
Temperature
Determined by engine sender
Engine Oil Pressure Determined by engine sender
Engine Speed Magnetic
Pickup
0 - 30 V pulse
External Start Momentary
N/O input
(momentary close to start)
External Stop Momentary
N/O input
(momentary close to stop)
External Start/Stop
Latching Toggle
N/O input (close to start and
run - open to stop)
OUTPUTS
Preheat Contactor 3A / 30 V DC / 250 V AC / (N/O)
Start Contactor 3A / 30 V DC / 250 V AC / (N/O)
Stop Contactor 3A / 30 V DC / 250 V AC / (N/O)
ENCLOSURE - VE.net module
Mounting DIN rail
Measurements 105 x 85 x 57 mm
Weight 200 g
Connector
Screw terminal strip for inputs/
outputs
2 x RJ45 for VE.Net, RJ11 for
sensing module connection
ENCLOSURE sensing module
Mounting DIN rail
Measurements 180 x 115 x 70 mm
Weight 200 g
Connector
Internal M6 studs for AC
connection
RJ11 for comms to VE.Net
module
VE.Net Generator Module